600A Bushing Extender can be installated on standard deenergized 600A deadbreak interfaces for coupling reducing tap plugs, connecting plugs and apparatus bushings. 200A Loadbreak interfaces for Elbow Surge Arrester and Elbow Connector. When assembled to mating apparats, it provides a completely shielded connection.
Order Information
Description | Reference No. | Voltage Rating | Current Rating |
15kV 600A Bushing Extender | UG BE-15/600 | 15kV | 600A |
25kV 600A Bushing Extender | UG BE-25/600 | 25kV | 600A |
Bom
– Bushing Extender
– Covering Cap
– Threaded Stud
– Cleaning Tissue
– Installation Instruction Sheet(Optional)
Electrical Characteristics
Voltage Rating | 15kV | 25kV |
Maximum Rating Phase-to-phase | 14.4kV | 26.3kV |
Maximum Rating Phase-to-ground | 8.3kV | 15.2kV |
AC 50Hz 1 Minute Withstand | 34kV | 40kV |
DC 15 Minute Withstand | 53kV | 78kV |
BIL and 1.5 / 50µs Impulse Withstand Voltage | 95kV | 125kV |
Partial Discharge Voltage | 11kV ( <3pC) | 19kV ( <3pC) |
Continuous Current | 600A | 600A |
24h Overload | 1000A | |
Short Time | 25kA rms sym. for 0.17s(60Hz)/0.2s(50Hz) 10kA rms sym. for 3.0s | |
Meets ANSI/IEEE 386 , latest version . |
Reviews
There are no reviews yet.