15(25)kV 600AMP Deadbreak T Connector Plug

The 600A Deadbreak T Connector Plugs are used to connect two or more 600A deadbreak terminators. Deadbreak Connector plugs are typically used in a separable splice, or with a bushing extender. to increase the distance from the apparatus front plate to the 600A terminator, easing cable training. Smei-conducting coating provides continuity with semi-conducting shield of EPDM rubber of mating parts.

The 600A Deadbreak T Connector Plugs are used to connect two or more 600A deadbreak terminators. Deadbreak Connector plugs are typically used in a separable splice, or with a bushing extender. to increase the distance from the apparatus front plate to the 600A terminator, easing cable training. Smei-conducting coating provides continuity with semi-conducting shield of EPDM rubber of mating parts.

 

Order Information

Description Reference No. Voltage Rating Current Rating
15kV 600A Deadbreak T Connector Plug UG DTP-15/600 15kV 600A
25kV 600A Deadbreak T Connector Plug UG DTP-25/600 25kV 600A

 

Electrical Characteristics

Voltage Rating 15kV 25kV
Maximum Rating Phase-to-phase 14.4kV 26.3kV
Maximum Rating Phase-to-ground 8.3kV 15.2kV
AC 50Hz 1 Minute Withstand 34kV 40kV
DC 15 Minute Withstand 53kV 78kV
BIL and 1.5 / 50µs Impulse Withstand Voltage 95kV 125kV
Partial Discharge Voltage 11kV ( <3pC) 19kV ( <3pC)
Continuous Current 600A 600A
24h Overload 1000A
Short Time 25kA rms sym. for 0.17s(60Hz)/0.2s(50Hz) 10kA rms sym. for 3.0s
Meets ANSI/IEEE 386 , latest version. Mate with bushing interface figure 11.

 

Bom

– Deadbreak T Connector Plug

– Threaded Stud

– Covering Cap

– Cleaning Tissue

– Silicone Lubricant

– Installation Instruction Sheet(Optional)