25kV/35kV 200A Rotatable Feedthru Insert can be connected with underground cable to distribution power system of pad-mound transformer, surrounding power supply branch box, using together with loadbreak elbow connector elbow surge arrester and appraatus bushing.
Order Information
Description | Reference No. | Voltage Rating | Current Rating |
25kV 200A Rotatable Feedthru Insert | UG FI-25/200 | 25kV | 200A |
35kV 200A Rotatable Feedthru Insert | UG FI-35/200 | 35kV | 200A |
Performance
25kV/35kV 200A Rotatable Feedthru Insert is used to provide dual bushings from a single apparatus bushing well. It makes converting radial-feed transformers to feedthru transformers and adding in-line arrester protection both easy and practical. Its patented, built-in torquelimiting ratchet prevents operators from accidentally breaking bushing well studs during installation. The Loadbreak Elbows are molded with high quality sulfurcured insulating and semi-conducting EPDM rubber, When mated with comparably rated products, the insert provides a fully shielded and submersible load break apparatus connection. The Rotatable Feedthru inserts latch indicator ring, located on the circumference of the bushing’s collar, eliminate the quesswork of loadbreak elbow installation on the bushing interface. The bright yellow ring provides immediate feedback to determine if the elbow is properly installed on the bushing. If the yellow ring is completely covered by the loadbreak elbow, it is fully “latched” if the ring is visible. The elbow can be installed correctly before any problem occur.
Electrical Characteristics
Voltage Rating | 25kV | 35kV |
Maximum Rating Phase-to-phase | 26.3kV | 36.6kV |
Maximum Rating Phase-to-ground | 15.2kV | 21.1kV |
AC 50Hz 1 Minute Withstand | 40kV | 50kV |
DC 15 Minute Withstand | 78kV | 103kV |
BIL and 1.5 / 50µs Impulse Withstand Voltage | 125kV | 150kV |
Partial Discharge Voltage | 19kV ( <3pC) | 26kV ( <3pC) |
Continuous Current | 200A | 200A |
Switching Current | 10 operations at 200A, 26.3kV | 10 operations at 200A, 36.6kV |
Fault Closure | 10kA | 10kA |
Short Time | 10kA rms sym. For 0.17s (60Hz) /
0.2s (50Hz) 3.5kA rms sym. for 3.0s |
10kA rms sym. For 0.17s (60Hz) / 0.2s (50Hz) 3.5kA rms sym. for 3.0s |
Meets ANSI / IEEE 386, latest version. Mate with bushing interface figure 7. |
Bom
– Rotatable Feethru Insert
– Covering Cap
– Silicone Lubricant
– Cleaning Tissue
– Stainless Steel Bail Assembly + M3 Screw + Dished Nut
– Grounding Wire
– Installation Instruction Sheet (Optional)
Reviews
There are no reviews yet.