35 kV Cold Shrinkage Indoor / Outdoor Termination

Apply to single-core/three-core armored or non-armored XLPE/EPR cable below 35kV.

Category:

Apply to single-core/three-core armored or non-armored XLPE/EPR cable below 35kV.

Performance test
Voltage 6/10(12)kV 8.7/15(17.5)kV 12/20(24)kV 18/30(36)kV
Partial discharge test at room temperature 10kV, <5pC 15kV, <5pC 20kV, <5pC 30kV, <5pC
power-frequency voltage test 27kV 5min 39kV 5min 54kV 5min 81kV 5min
impulse voltage test 75kV ± 10 times 95kV ± 10 times 125kV ± 10 times 170kV ± 10 times

 

Dimensions
6/10(12)kV
Indoor Termination Outdoor Termination Cable insulation OD(mm) Cross section(mm²)
UG-IT-10kV-1 UG-OT-10kV-1 16.5-19.7 70-95
UG-IT-10kV-2 UG-OT-10kV-2 19.7-23.5 120-150
UG-IT-10kV-3 UG-OT-10kV-3 22.5-31.3 185-300
UG-IT-10kV-4 UG-OT-10kV-4 28.9-38.0 400-630
8.7/15(17.5)kV
Indoor Termination Outdoor Termination Cable insulation OD(mm) Cross section(mm²)
UG-IT-17.5kV-1 UG-OT-17.5kV-1 16.5-19.7 25-50
UG-IT-17.5kV-2 UG-OT-17.5kV-2 19.7-23.5 70-120
UG-IT-17.5kV-3 UG-OT-17.5kV-3 22.5-31.3 150-300
UG-IT-17.5kV-4 UG-OT-17.5kV-4 28.9-38.0 400-500
12/20(24)kV
Indoor Termination Outdoor Termination Cable insulation OD(mm) Cross section(mm²)
UG-IT-24kV-1 UG-OT-24kV-1 19.7-23.5 35-50
UG-IT-24kV-2 UG-OT-24kV-2 22.5-31.3 70-150
UG-IT-24kV-3 UG-OT-24kV-3 28.9-38.0 185-400
UG-IT-24kV-4 UG-OT-24kV-4 38.0-44.1 500-630
18/30(36)kV
Indoor Termination Outdoor Termination Cable insulation OD(mm) Cross section(mm²)
UG-IT-36kV-1 UG-OT-36kV-1 25.9-33.9 50-150
UG-IT-36kV-2 UG-OT-36kV-2 33.7-41.3 185-300
UG-IT-36kV-3 UG-OT-36kV-3 41.3-47.0 400-500
UG-IT-36kV-4 UG-OT-36kV-4 47.0-53.5 630